Technical Data and dimensions Output Voltage DC-Bus Voltage Speed Frequency Climatic Category Ambient Temp. Protection Class Terminals Motor cable length RFI class max. 3x 400 V~ +25 %, sinusoidal max. 650 Vdc max. 120 Hz min. 6 kHz 25/085/21 max. + 40 °C IP20 Touch Protected Screwing Terminals unlimited C1 (without cable screening) Type Filter nominal current 50-120 Hz 2.5 4 7 10 13 16 25 35 40 50 Frequency minimal kHz 6 6 6 6 6 6 6 6 6 6 Typical VLT® nominal output and -current FC 302 kW 1,1 1.5 - 2.2 3-4 5,5 7,5 11 15 18 22 30 A1 3 4.1 - 5.6 7.2 - 10 13 16 24 32 37.5 44 61 • • Power loss W 80 95 110 140 200 245 270 330 345 390 Weight Height (A) mm 268 268 268 268 268 268 399 399 399 545 Width (B) mm 118 118 147 147 176 176 230 230 230 325 Depth (C) mm 193 193 205 205 205 205 245 245 245 242 kg 8 9 12 13 17 18 28 30 31 71 192H5410 192H5411 192H5412 192H5413 192H5414 192H5415 192H5416 192H5417 192H5418 192H5419 1 Nominal current of the frequency converter without derating Overload: 1.6 times Ir for 60s every 10 minutes Please ask, if you need higher voltage or higher power sizes Danfoss VLT Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80 www.danfoss.com/drives, E-mail: info@danfoss.com DEDD.PFP.653.A2.02 VLT® is a registered trademark of Danfoss A/S 2015.03